Rockwell Automation 1413-CAP-ME-PE Capacitor Bank Controller, Series C User Manual

Page 35

Advertising
background image

Rockwell Automation Publication 1413-UM001D-EN-P - November 2010

35

Configuration Chapter 3

N7:10

Capacitor Step 1 -
Effective Size

kVAR

Nameplate capacitor size for each step

Yes

50

Configuration

N7:11

Capacitor Step 2 -
Effective Size

kVAR

Yes

(2)

50

Configuration

N7:12

Capacitor Step 3 -
Effective Size

kVAR

Yes

(2)

50

Configuration

N7:13

Capacitor Step 4 -
Effective Size

kVAR

Yes

(2)

50

Configuration

N7:14

Capacitor Step 5 -
Effective Size

kVAR

Yes

(2)

50

Configuration

N7:15

Capacitor Step 6 -
Effective Size

kVAR

Yes

(2)

50

Configuration

N7:16

Capacitor Step 7 -
Effective Size

kVAR

Yes

(2)

50

Configuration

N7:17

Capacitor Step 8 -
Effective Size

kVAR

Yes

(2)

50

Configuration

N7:18

Capacitor Step 9 -
Effective Size

kVAR

Yes

(2)

50

Configuration

N7:19

Capacitor Step 10 -
Effective Size

kVAR

Yes

(2)

50

Configuration

N7:30

Capacitor
Discharge Time

seconds

The amount of time after a capacitor step is
turned off, before a capacitor step is
considered fully discharged

Yes

60

Configuration

N7:31

Nominal Voltage

volts

The nominal bus voltage of the system

Yes

480

Ext Configuration 1

N7:32

Voltage Threshold
- High and Low

%

The voltage percentage from nominal, that
will determine high and low limits for
alarming

Yes

1…10

5

Ext Configuration 1

N7:34

Lead Deadband

kVAR

The leading kVAR limit allowed for the
system, before the controller acts to correct
lead, typically 33% of smallest capacitor step

Yes

20

Configuration

N7:35

Lag Deadband

kVAR

The lagging kVAR limit allowed for the
system, before the controller acts to correct
lag, typically 66% of largest capacitor step

Yes

35

Configuration

N7:36

Step Tolerance
Low Limit

%

The kVAR percentage of effective, that will
determine low limits for each capacitor step

Yes

0…10

5

Ext Configuration 2

N7:37

Power Factor Out-
of-Range Time

seconds

The amount of time the system kVAR must be
out of the range of the lead or lag deadband,
before the controller acts to correct

Yes

60

Ext Configuration 1

N7:39

Step Tolerance
Time

seconds

The amount of time after a capacitor step is
actuated, before taking a sample reading of
the system kVAR difference, to determine if
the capacitor step is above the step tolerance
low limit

Yes

30

Ext Configuration 2

N7:40

Voltage High In-
Range Time

seconds

The amount of time the bus voltage must be
below the high limit before resetting the
Voltage High Alarm

Yes

120

Ext Configuration 1

N7:41

Voltage Low In-
Range Time

seconds

The amount of time the bus voltage must be
above the low limit before resetting the
Voltage Low Alarm

Yes

120

Ext Configuration 1

Table 9 - Control and Status Parameters

Address

Parameter

Unit

Description

Configurable Range

Default

PanelView
Component
Screen