Rockwell Automation 1413-CAP-ME-PE Capacitor Bank Controller, Series C User Manual

Page 49

Advertising
background image

Rockwell Automation Publication 1413-UM001D-EN-P - November 2010

49

Configuration Chapter 3

5.

Press Auto Detect kVAR to navigate to the Auto Configure Effective
kVAR process.

6.

Follow steps 1…3 on this screen, then press Auto Detect Cap Size to
initiate the auto-configuration process.

7.

Navigate to the Extended Status screen and write down the Measured
kVAR for each of your capacitor banks.

8.

Navigate to the Configuration screen and configure the steps with the
measured kVAR data.

TIP

The number of measurements to average for each step is entered
on the Extended Configuration Screen #2 (F10).