Parameter descriptions -29, Programming – Rockwell Automation 1336R REGEN LINE REG User Manual

Page 45

Advertising
background image

Regenerative DC Bus Supply Operation

2–29

Programming

Parameter No.

1

Display Units

bits

Parameter Type

Read/Write

Factory Default

XXXXX000

Regen Brake Mode

Min/Max Value

N/A

Drive Units

000 = 0

bin

Operational Mode

Sets the 1336 REGEN Line Regeneration Package mode of operation. The modes are defined
by the last (3) bits of a 16 bit word. To set the mode, first stop the 1336 REGEN Converter, set
the mode, then re-enable the converter.

Important: If the [Operational Mode] is reset while the 1336 REGEN Converter is enabled,

a System Mode Change Fault will occur. Issuing a reset command will clear the
fault and reset the converter.

Parameter No.

2

Display Units

Amps

Parameter Type

Read Onl

y

Drive Units

1 = 0.1A

Rated AC Line Current

Displays the rated AC line current of the 1336 REGEN Converter.

Parameter No.

3

Display Units

%

Min/Max Value

-200/200

Parameter Type

Read Only

Drive Units

100 = 4096

AC Line Current

Displays the actual I

q

AC line current in percent of rated AC line current. Positive values

indicate motoring — Negative values indicate regeneration.

Parameter No.

4

Display Units

%

Min/Max Value

-200/200

Parameter Type

Read Only

Drive Units

100 = 4096

Peak Load

Displays the peak motoring or regenerating current in percent of rated AC current. The peak
value is held for five seconds. Positive values indicate motoring — Negative values indicate
regenerating.

i o n a l M o d e

t

p e r a

O

0 0

1

0

X X X 0

X

Bit 2

Bit 1

Bit 0

0 = Regen Brake Mode

1 = Regen DC Bus Supply Mode

0 = Fixed DC Bus Mode

1 = DC Bus Trim Mode

0 = 460VAC Input Line Voltage

1 = 380VAC Input Line Voltage

0 = Fixed DC Bus

1 = Scheduled DC Bus

0 = Voltage Gain

1 = Voltage Gain

Bit 3

C u r r e n t

a t e d

R

0 A M P S

2

.

0 0

u r r e n t

C

i n e

L

1 0 0 %

3

+

o a d

L

e a k

P

1 0 0 %

4

+