Programming – Rockwell Automation 1336R REGEN LINE REG User Manual

Page 46

Advertising
background image

2–30

Regenerative DC Bus Supply Operation

Programming

Parameter No.

5

Display Units

Volts

Parameter Type

Read Only

Drive Units

1 = 0.1V

Actual Bus Voltage

Displays the actual voltage on the DC bus in DC volts.

Parameter No.

6

Display Units

Volts

Parameter Type

Read/Write

Factory Default

380VAC Input = 607V
460VAC Input = 735V

Min/Max Value

380VAC Input = 548/634V
460VAC Input = 663/767V

Drive Units

100 = 4096

Bus Voltage Reference

This parameter sets the DC bus voltage. It allows the DC Bus voltage to be set to 2-18% higher
than the DC Base volts while the 1336 REGEN Converter is enabled.

For 380VAC input Line Regeneration Packages, DC

BASE

volts = 537V.

For 460VAC input Line Regeneration Packages, DC

BASE

volts = 650V.

Important: This parameter is effective only in the Fixed DC Bus Mode.

Parameter No.

7

Display Units

Number

Parameter Type

Read/Write

Factory Default

1.00

Min/Max Value

0.50/2.00

Drive Units

1.00 = 4096

Proportional Gain

This parameter sets the proportional gain for the PI DC Bus Voltage Regulator, and may be set
while the 1336 REGEN Converter is enabled. Increasing the gain increases the response
speed of the DC Bus Voltage Regulator, but may also cause the bus voltage to overshoot.

Parameter No.

8

Display Units

Number

Parameter Type

Read/Write

Factory Default

1.00

Min/Max Value

0.50/2.00

Drive Units

1.00 = 4096

Integral Gain

This parameter sets the integral gain for the PI DC Bus Voltage Regulator, and may be set
while the 1336 REGEN Converter is enabled. Increasing the gain increases the response
speed of the DC Bus Voltage Regulator, but may also cause the bus voltage to overshoot.

l t s A c t .

o

u s V

B

0 V O L T

5

.

7 3 5

e g R e f .

R

u s V

B

0 V O L T

6

.

7 3 5

e g K P

R

u s V

B

0

7

0

1 .

e g K I

R

u s V

B

0

8

0

1 .

Advertising