Regenerative brake startup – Rockwell Automation 1336R REGEN LINE REG User Manual

Page 84

Advertising
background image

3–32

Regenerative Brake Operation

Regenerative Brake
Startup

7. From the status display, press or any other key.

will be displayed.

8. Press the until is

displayed.

9. Press

10. Press the until is

displayed.

11. Press to restore all parameters to their original factory

settings.

12. Press once to exit back to the status display.

After the parameters have been restored to their factory settings,
the status display will show

To Enable the converter, present a logic “high” to terminal 4 of
J15.

At the factory default settings, the 1336 REGEN Package is
programmed for 460VAC line power and set to the Regenerative
Brake mode of operation.

• For 380VAC operation, set Bit 2 of P-1

[Operational Mode]

to 1. No

other parameter changes are required.

To view a parameter other than

P-5 [Bus Volts Act.]

on the HIM

display,

P-28 [HIM Display Prm]

may be changed. Setting parameter 28

to a different parameter number will display that parameter’s value
on line 2 of the status display.

M o d e

e

h o o s

C

y

a

i s p l

D

or

M o d e

e

h o o s

C

m

E P r o

E

or

m

E P r o

E

D e f a u l t s

e s e t

R

a b l e d

n

o t E

N

0 . 0 V O L T

5

6