Programming – Rockwell Automation 1336R REGEN LINE REG User Manual

Page 51

Advertising
background image

Regenerative DC Bus Supply Operation

2–35

Programming

Parameter No.

27

Display Units

Bits

Parameter Type

Read/Write

Factory Default

11100

Min/Max Value

N/A

Drive Units

N/A

Fault Select 1

This parameter enables or disables faults as defined by the first (5) bits of a (16) bit word. The
[Fault Select1] parameter may be set while the 1336 REGEN Converter is enabled.

Parameter No.

28

Display Units

Number

Parameter Type

Read/Write

Factory Default

5

Min/Max Value

1/32

Drive Units

N/A

HIM Default Display Parameter

This parameter sets which of the previous parameters will be displayed after 1336 REGEN
Converter power-up. The [HIM Display Param] parameter may be set while the 1336 REGEN
Converter is enabled.

S e l e c t 1

a u l t

F

0 0

2 7

1

X X 1 1

X

Bit 2

Bit 1

Bit 0

0 = SCANport 1 Timeout Disabled

1 = SCANport 1 Timeout Enabled

0 = SCANport 2 Timeout Disabled

1 = SCANport 2 Timeout Enabled

0 = Phase Mismatch Fault Disabled

1 = Phase Mismatch Fault Enabled

0 = Open Precharge Fuse Fault Disabled1 = Open Precharge Fuse Fault Enable
0 = PLL Fault Disabled

1 = PLL Fault Enabled

Bit 3

Bit 4

s p l a y P r m

i

I M D

H

5

2 8