Troubleshooting – Rockwell Automation 1336R REGEN LINE REG User Manual
Page 98

4–6
Troubleshooting
Troubleshooting
Fault & Code No.
Status
Indicates
Action
Host/DSP Handshake
On
3 Flashes 3 Flashes Don’t
Care
Host processor and DSP
handshake error.
Reset and re-enable the
Converter.
If the fault occurs again, replace
the Converter Control Board.
SP1 Timeout
F 48
On
N/A
N/A
Flashing
The SCANport device connected
to SCANport 1 has been
disconnected and the mask bit for
SCANport 1 is set.
If the SCANport device was not
intentionally disconnected, do the
following:
1. Check the wiring between
SCANport1 and the SCANport
device. Replace wiring if
required.
2. Clear bit 0 of P27 - [Fault
Select1] to disable this fault
from occurring.
SP2 Timeout
F 49
On
N/A
N/A
Flashing
The SCANport device connected
to SCANport 2 has been
disconnected and the mask bit for
SCANport 2 is set.
If the SCANport device was not
intentionally disconnected, do the
following:
1. Check the wiring between
SCANport1 and the SCANport
device. Replace wiring if
required.
2. Clear bit 1 of P27 - [Fault
Select1] to disable this fault
from occurring.
Sys. Mode Change
F 50
On
N/A
N/A
Flashing
P1 - [Operational Mode] was
changed.
Reset and re-enable the
Converter.
DS1
FAULT
DS2
ENABLE
DS3
STATUS
DS4
COM