Regenerative brake sizing – Rockwell Automation 1336R REGEN LINE REG User Manual

Page 57

Advertising
background image

Regenerative Brake Operation

3–5

Regenerative Brake
Sizing

6. Determine the required percent of braking torque (

TQ%

).

TQ% =

TQ

B

×

100

——————

TQ

M

Where

TQ

B

=

The Required Braking Torque

TQ

M

=

The Rated Motor Torque

7. Determine the peak braking horsepower (

HP

2

).

HP

2

=

TQ

B

×

N

1

——————

5250

Where

TQ

B

=

The Required Braking Torque

N

1

=

The Maximum Motor Speed

8. Calculate the peak AC line current (

I

1

).

The AC line current of the 1336 REGEN Package will be at its
maximum value at the beginning of the deceleration period.

I

1

=

HP

1

×

746

———————
V

L-L

× √

3

Where

HP

1

=

The Peak Braking HP

V

L-L

=

The Line-to-Line Utility Voltage

If your application requires continuous regeneration, (

I

1

) must be

less than the rated current of the 1336 REGEN Package. Pick a
1336 REGEN Package that has an AC line current rating greater
than or equal to (

I

1

) at the appropriate AC line voltage.

If your application does not require continuous regeneration,
continue on to Step 9.

See page 3-8 for information on paralleling regenerative brakes.

9. The 1336 REGEN Package has a peak overload current rating

(

I

OL

) of 150% of its data nameplate rating.

I

OL

=

I

RATED

×

1.5

Where

I

RATED

=

The nameplate current of the 1336 REGEN

Package