Troubleshooting

4–5

Troubleshooting

Fault & Code No.

Status

Indicates

Action

Illegal Drv.

Type

F 34

On

N/A

N/A

Flashing

The power structure is not
supported.

1. Check that the Converter

Control Board and Gate Driver
Board are matched and
correspond to the Converter
frame size.

2. Reset and re-enable by:

a.Exiting to the EEProm Mode.
b. Resetting defaults.
c. Verifying that P1 is set to the

correct operating mode.

d. Resetting the Converter.

If the fault occurs again, replace
the Converter Control Board.

SW Malfunction

F 35

On

N/A

N/A

Flashing

Software error.

Reset and re-enable the Converter.
If the fault occurs again, replace the
Converter Control Board.

Host/DSP Com Err

F 37

On

N/A

N/A

Flashing

Host processor unable to
communicate with the Converter
SCANport.

Reset and re-enable the Converter.
If the fault occurs again, replace the
Converter Control Board.

PwrUp DspCom Err

F 38

On

N/A

N/A

Flashing

Host processor unable to
communicate with the Converter
SCANport.

Reset and re-enable the Converter.
If the fault occurs again, replace the
Converter Control Board.

EE Checksum

F 39

On

N/A

N/A

Flashing

1336 REGEN Converter parameter
database is corrupt.

Reinitialize Converter parameters

or:

1. Recall values.

2. Save values.

3. Reset and re-enable the

Converter.

If the fault occurs again, replace the
Converter Control Board.

Pwr Up Marker

F 40

On

N/A

N/A

Flashing

Fault queue text.

N/A

Unknown Error

F 41

On

N/A

N/A

Flashing

Fault queue text.

Reset and re-enable the Converter.
If the fault occurs again, replace the
Converter Control Board.

No Entry

F 42

On

N/A

N/A

Flashing

Fault queue text.

N/A

Clear Faults

F 43

On

N/A

N/A

Flashing

Fault queue text.

N/A

DS1

FAULT

DS2

ENABLE

DS3

STATUS

DS4

COM