Regenerative Brake Operation

3–11

380-480VAC Power
Wiring

Grounding

All 1336 REGEN components must be connected to system
ground at the PE power ground terminal provided. Ground
impedance must conform to the requirements of national and local
industrial safety regulations (NEC, CENELEC, etc.), and should
be inspected and tested at appropriate intervals. In any cabinet, a
single low-impedance ground point or ground bus bar should be
used. All circuits should be grounded independently and directly.
The AC supply ground conductor should also be connected
directly to this ground point or bus bar.

Fig re 3 4 — Regenerative Brake Gro nding

PE

PE

GND

GND

PE

Conduit/4-Wire Cable

Nearest

Building Structure Steel

USER

SUPPLIED

120V AC

1336 REGEN

Converter

1321 3%

Line Reactor

GND

1

(2) jumpers connect PE and TE at the 1336 REGEN
Converter Main Terminal Block. Consult
Allen-Bradley Application Engineering prior
to removing either jumper.

S2

TORQUE TERM. TO 6 N-m (52 lb-in)

T2

USE 75

°

C COPPER WIRE ONLY

R2

DC–

DC+

TE

PE

PE

120

RT

N

120

VA

C

1

1

PE

PE

AC DRIVE

PE

1336 REGEN

Precharge

R1

S1

T1

A1

B1

C1

A2

B2

C2

R2

S2

T2

+DC

+DC

–DC

–DC

1

PE TE

R

S

T

TB1-1
TB1-3

120V

AC

120 RTN

D Frame

2

2

Important:

If you are using a Regenerative Brake with a B Frame
AC drive, refer to the Power-up Sequence on page 3-3.

Sensitive Circuits

It is essential to define paths
through which high frequency
ground currents flow to ensure that
sensitive circuits do not share a
path with these currents. Control
and signal conductors should not
be run near or parallel to power
conductors.

TE (True Earth) Termination

The converter’s TE terminals are
used for all control signal shields
internal to the 1336 REGEN
Converter and must be connected
to the converter’s TE
terminals by a separate
continuous lead.

PE (Power Earth) Termination

A safety ground is required by
code. This point must be
connected to adjacent building
steel or a floor ground rod
provided grounding points comply
with NEC and local regulations.