Rockwell Automation 1500 Modular Protection System Conversion Kit (GE Multilin to Bulletin 825 Plus) User Manual
Page 16
![background image](/manuals/578523/16/background.png)
1500-IN059C-EN-E – June 2013
4-
Installation
Disconnect and lockout all sources of power entering the low
voltage compartment where the GE Multilin relay is located.
This may include opening the main disconnect of isolation
switch. Failure to disconnect and lock out power can result
in personal injury and/or damage to the equipment.
1. Disconnect the control wires connected to the GE Multilin relay. Using the
wire number table in Appendix A, mark each wire with the corresponding
GE Multilin relay terminal block number for reference later in the proce-
dure.
2. Remove mounting hardware.
3. Remove the GE Multilin relay from the low voltage door.
Save all the mounting hardware.
Figure 4. – Typical Existing LV door layout with 69 Plus Relay
Removing Low Voltage
Door Components
ATTENTION