825 Plus RTD Scanner • Installation Guide

Failure to follow these steps can result in damage to the

equipment and/or personal injury.

1. Ensure the RTD wires are disconnected from the GE Multilin MPM/MTM

module. Using the wire number table in Appendix C, mark each wire with

the corresponding GE Multilin relay terminal block number.

2. Mount the 825 Plus RTD Scanner in an appropriate location within the low

voltage compartment. The 825 Plus RTD scanner may be mounted remote

from the controller, i.e. near the motor.

3. Route and connect the supplied fibre optic cable between the 825 Plus RTD

scanner and the 825 Plus relay. (Figure C.1)

4. Reroute and connect the RTD wires to the corresponding 825 Plus RTD

Scanner terminal blocks. Use the wire number table created in step 1 to

verify the wire numbers and the terminal block location.

5. Refer to the electrical diagrams and the RTD wire number cross-reference

table provided to ensure proper connections.

Installation Instructions

Figure C.1

A T T E N T I O N