Reconnecting existing control circuit – Rockwell Automation 1500 Modular Protection System Conversion Kit (GE Multilin to Bulletin 825 Plus) User Manual

Page 22

Advertising
background image

1500-IN059C-EN-E – June 2013

4-8

Installation

Reconnecting Existing Control Circuit

1. Using the provided spiral wrap, combine the existing and new door control

wire bundle. (Figure 4.21)

2. Re-route the existing control wiring to the existing door components

and through the 825 Plus interface panel. Care must be taken to ensure

enough space to allow door closure. (Figures 4.21 and 4.22)

3. Secure the existing wiring to the door with provided sticky pads and tie

wraps. The top right mounting tie wrap can be used to affix the existing

wiring with the special tie wrap supplied. (Figur

es 4.23 and 4.24)

4. Reconnect the existing wires to the corresponding 825 Plus Interface

Panel terminal blocks. These are located and numbered the same as

those on the GE Multilin relays. Use the wire number table (created as

part of the procedures in Appendix A) to verify the wire numbers and the

terminal block location.