Installation
Reconnecting Existing Control Circuit
1. Using the provided spiral wrap, combine the existing and new door control
wire bundle. (Figure 4.21)
2. Re-route the existing control wiring to the existing door components
and through the 825 Plus interface panel. Care must be taken to ensure
enough space to allow door closure. (Figures 4.21 and 4.22)
3. Secure the existing wiring to the door with provided sticky pads and tie
wraps. The top right mounting tie wrap can be used to affix the existing
wiring with the special tie wrap supplied. (Figur
es 4.23 and 4.24)
4. Reconnect the existing wires to the corresponding 825 Plus Interface
Panel terminal blocks. These are located and numbered the same as
those on the GE Multilin relays. Use the wire number table (created as
part of the procedures in Appendix A) to verify the wire numbers and the
terminal block location.