Installation instructions – Rockwell Automation 1500 Modular Protection System Conversion Kit (GE Multilin to Bulletin 825 Plus) User Manual
Page 34

1500-IN059C-EN-E – June 2013
C-2
825 Plus RTD Scanner • Installation Guide
Failure to follow these steps can result in damage to the
equipment and/or personal injury.
1. Ensure the RTD wires are disconnected from the GE Multilin MPM/MTM
module. Using the wire number table in Appendix C, mark each wire with
the corresponding GE Multilin relay terminal block number.
2. Mount the 825 Plus RTD Scanner in an appropriate location within the low
voltage compartment. The 825 Plus RTD scanner may be mounted remote
from the controller, i.e. near the motor.
3. Route and connect the supplied fibre optic cable between the 825 Plus RTD
scanner and the 825 Plus relay. (Figure C.1)
4. Reroute and connect the RTD wires to the corresponding 825 Plus RTD
Scanner terminal blocks. Use the wire number table created in step 1 to
verify the wire numbers and the terminal block location.
5. Refer to the electrical diagrams and the RTD wire number cross-reference
table provided to ensure proper connections.
Installation Instructions
Figure C.1