Equipment Description

Overview

This chapter describes the features of the GE Multilin to Bulletin 825 Plus
Conversion Kit.

Operational Requirements

Monitoring application parameters and process data of an installation is very
important. Even a slight change in the starting and operating behavior of the
motor can indicate an impeding fault. The Bulletin 825 Plus helps eliminate
the potential trouble before major repairs are necessary and loss of production
occurs.

The Bulletin 825 Plus fulfills these requirements by providing the following
protective functions:
• High overload, stalling
• Underloading
• Wrong direction of rotation

However, the Bulletin 825 Plus functionality does not directly correspond to the
GE Multilin relays. Below is a summary of some of the features offered by the
Bulletin 825 Plus.

GE Multilin

Function Description

169/269/269 Plus

369

Bul. 825 Plus

Parameters

Current Transformer (Primary)

20A – 1500A

1A – 5000A

0.5 A – 5000 A

Full Load Current (FLC)

10A – 1000A

1A – 5000A

0.5 A – 5000 A

Thermal Overload Protection

Yes

Yes

Yes

Overcurrent Protection

Yes

Yes

Yes

Allowable Acceleration Time

0.5 – 125 s

1 – 250 s

1s – 240s

Allowable RTD types

10

Ω Cu, 100 Ω Ni,

120

Ω Ni, 100 Ω PI

10

Ω Cu, 100 Ω Ni,

120

Ω Ni, 100 Ω PI

10

Ω Cu, 100 Ω Ni,

120

Ω Ni, 100 Ω PI

Number of WindingRTDs

1 – 6

1 – 6 w/RTD option

1 – 12 ™

Number of Bearing RTDs

1 – 2

1 – 4 w/RTD option

1 – 12 ™

Allowable Number of Starts

1 – 5 (starts per hour)

1 – 5 (starts per hour)

1 – 15 (starts per hour)

Phase Unbalance Trip Current

4 – 30 (percent of FLC)

4 – 30 (percent of FLC)

5 – 80 (percent of FLC)

Phase Unbalance Alarm Current

4 – 30 (percent of FLC)

4 – 30 (percent of FLC)

5 – 80 (percent of FLC)

Phase Reversal Protection

Yes (w/metering option)

Yes (w/metering option)

Yes

™

Total of twelve (12) inputs for winding, bearing or other RTD.