Bul. 937C Transmitter Supply Converter Installation Instructions

The device measures in mA. If you have selected different units, the device calculates the measured value in the
selected units using the parameters Zero point and Conversion factor.

The parameters for you application must be determined according to the following formula:

An arbitrary value between -15 mA and +15 mA can be set as the Zero point, and values between 0.100

and 5000 as the Conversion factor.

The following includes examples where the formulas are applied.

Measured value in

the selected units

Editing device data: Input

Line monitor

If you select On for LB,an input current <0.2 mA will be registered as a lead break.

If you select On for SC,an input current >0.22 mA will be registered as a short circuit.

If you wish to process the <0.2 mA input values as measured values, you must deselect the lead

breakage deterction (Off LB). If not, an error will be signalled within the measuring range.

=(Original measured value{mA] - Zero point) x Conversion factor


Zero point and Conversion factor