Fault current

The following table shows the current output in the event of a fault, depending on the characteristic.

Start value and End value

Please note when entering Start value and End value:
Both values are to be entered in the units, which were selected under Units.
Values between 0 mA and 20 mA can be entered, or between the values of these limits converted

into the selected units, using the parameters Zero point and Conversion factor.

The difference between End value and Start value must be at least 1 % of the End value (preset

automatically by the transmitter supply converter).

Setting

0 mA ... 20 mA

4 mA ... 20 mA NE43

4 mA ... 20 mA

Up/Down

21.5 mA

21.5 mA

22 mA

with short-circuit

with short-circuit

with short-circuit

(not distinguishable from

End value overrange)

0 mA

2.0 mA

0 mA

with lead breakage

with lead breakage

(not distinguishable from

Start value measurement)

with lead breakage

(not distinguishable from

Start value underrange)

Hold

Last measured value before the fault

Max

21.5 mA

21.5 mA

22 mA

(not distinguishable from

End value overrange)

Min

2.0 mA

0 mA

(not distinguishable from

Start value measurement)

0 mA

(not distinguishable from

Start value underrange)