Example 1: selected unit °C, 0 °C ... 200 °C is to correspond to 4 mA ... 20 mA

y = m x + n

• Conversion factor = rise in the graph

m = (y2 – y1) / (x2 – x1)

m = (200 – 0) / (20 – 4) = 12.5

• Zero point = intersection point with the x-axis on the graph, providing that the physical measuring

range starts from 0 (y = 0 °C). The zero point corresponds to the lower measuring range limit (x = 4

mA) from which the measuring range starts.

The zero point can be calculated as follows: n =

y – m x

n = 200 – 12.5 x 20 = -50

y = m x + n

x = (y – n) / m

x = (0 + 50) / 12.5 = 4

2

1

9

8

7

6

5

4

3

10

-1

50

100

150

200

-200

-150

-100

-50

-4 -3 -2

11 12 13 14 15 16 17 18 19 20

x [mA]

y [°C]