Editing device data: Input
Example 1: selected unit °C, 0 °C ... 200 °C is to correspond to 4 mA ... 20 mA
•
y = m x + n
• Conversion factor = rise in the graph
m = (y2 – y1) / (x2 – x1)
m = (200 – 0) / (20 – 4) = 12.5
• Zero point = intersection point with the x-axis on the graph, providing that the physical measuring
range starts from 0 (y = 0 °C). The zero point corresponds to the lower measuring range limit (x = 4
mA) from which the measuring range starts.
The zero point can be calculated as follows: n =
y – m x
n = 200 – 12.5 x 20 = -50
y = m x + n
x = (y – n) / m
x = (0 + 50) / 12.5 = 4