Default settings – Rockwell Automation 937CU-AITXF-DC1 Transmitter Supply Converter Installation Instructions User Manual
Page 32
Advertising
30
Bul. 937C Transmitter Supply Converter Installation Instructions
Menu
Parameter
Default setting
Separate value
Main menu
Unit
mA
Input
Line monitor
On LB/On SC
Zero point
4.000 mA
Conversion factor
0.100
Linearization
Off
Smoothing
3 s
Output Rel1
Min/Max (= switching direction) Min
Trip
16.00 mA
Hysteresis
2.000 mA
Mode
Passive
Alarm freeze
Off
Delay
0 s
Output Rel2
Min/Max (= switching direction) Min
Trip
2.000 mA
Hysteresis
2.000 mA
Mode
Active
Alarm freeze
Off
Delay
0 s
Output Iout
Characteristics
4 mA ... 20 mA NE43
Editing device data: Default settings
Default settings