Bul. 937C Transmitter Supply Converter Installation Instructions

Operating behaviour

The switching direction can be set as Max or Min and the direction of action as Active or Passive .

Application ranges:

• Switching direction Max, mode of operation Active:

alarm on trip value overrange, e. g. audible alarm on

• Switching direction Max, mode of operation Passive:

switch off on trip value overrange, e. g. pump, heating, ... off; with large

hysteresis Min/Max operation (pump, heating, ... on/off)

• Switching direction Min, mode of operation Active:

alarm on trip value underrange, e. g. audible alarm on

• Switching direction Min, mode of operation Passive:

switch off on trip value underrange, e. g. pump, heating, ... off; with

large hysteresis Min/Max operation (pump, heating, ... off/on)

Alarm freeze

——

On

Off

Delay

——

0 s ... 250 s

2