Bul. 937C Transmitter Supply Converter Installation Instructions

Example of a diagram of a mA measurement range on the output signal
Characteristic 4 mA ... 20 mA NE43, start value 2 mA, end value 10 mA

Example diagram displaying the input signal in °C to the output signal
Characteristic 4 mA ... 20 mA NE43, start value 0 °C, end value 200 °C.

Characteristic

Start value

converted into

End value

converted into

Linear

underrange up to

Linear overrange

up to

0 mA ... 20 mA

0 mA

20 mA

0 mA

20.5 mA

4 mA ... 20 mA

NE43

4 mA

20 mA

3.8 mA

20.5 mA

4 mA ... 20 mA

4 mA

20 mA

0 mA

approx. 22 mA

4.0

3.8

0

20.0

20.5

-1.9

2

Start value

10

End value

mA
Measuring
range

10.25

mA

4.0

3.8

0

20.0

20.5

-2

0

Start value

200

End value

°C
Measuring
range

205