background image

Installing the DeviceNet Option

2-5

Figure 2.5 Reconnecting the Cover

2. Tighten the screws on the cover to 1.46 Nm (13 in.-lb.).

Applying Power

1. Apply power to the network.

2. Apply power to the 1329I unit. The DeviceNet option receives its power

from the 1329I unit and from the network. When you apply power to the
option for the first time, the COMM status indicator flashes green for 1/4
second, red for 1/4 second, and then goes blank while the option finishes
its initialization. If it goes red, there is a problem. Refer to

Chapter 7

.

3. Verify that the option is set for the correct data rate and has a unique

node address. If a new data rate or address is needed, reconfigure the
option switches (

Commissioning the 1329I Unit for DeviceNet

in this

chapter). If switches 7 and 8 are On, create a point-to-point connection to
the option with a configuration tool to set its data rate and node address
parameters (

Chapter 3

).

4. Apply power to the master device (scanner) and other network devices.

1.46 Nm

(13 in-lb)

Display Cable

!

ATTENTION: Risk of equipment damage, injury, or
death exists. Unpredictable operation may occur if you
fail to verify that connections and switch settings are
compatible with your application. Verify that connections
and parameter settings are compatible with your
application before applying power to the 1329I unit.

Advertising