Rockwell Automation 1329I DeviceNet Option FRN 1.XXX User Manual
Page 80

C-18
DeviceNet Objects
Class Code 0x29 – Control
Supervisor Object
(Continued)
Instance 1 Attributes (Continued)
Common Services
State Transition Diagram
The following State Transition Diagram provides a graphical description of
the states and state transitions that are reflected in attribute #6.
Figure 3.1 State Transition Diagram
Attribute ID Access Rule Name
Data Type
Value
14
Get
Warn Code
UINT
0
15
Get
Ctrl From Net BOOL
0 = TB or keypad control
1 = Network control
16
Get/Set
DNet Fault
Mode
USINT
0 = Fault and Stop
1 = Ignore
17
Get/Set
Force Fault/
Trip
BOOL
0 -> 1 = Force fault
102
(1)
Get/Set
DNet Preset
Command
USINT
0 to 7
103
(1)
Get/Set
DNet Speed
Ref RPM
UINT
0 to 3600 (RPM)
104
(1)
Get/Set
DNet Speed
Ref Hz
UINT
0 to 120.0 (0.1 Hz)
(1)
This attribute can be set only when the expected packet rate (EPR) for the explicit connection is non-zero and
the 1329I does not have an active I/O connection.
Service Code
Implemented for
Service Name
Class
Instance
0x05
No
Yes
Reset
0x0E
Yes
Yes
Get_Attribute_Single
0x10
No
Yes
Set_Attribute_Single
Switch Power On
Ready
Enabled
Faulted
Switch Power Off
Fault Reset
Fault Detected
Fault Detected
Stop Complete
Run
Non-Existent
Stopping
Fault Detected
No Run
Run