Publication 1769-RM016A-EN-P - July 2006

32 Installation and Wiring

6. Move the bus lever fully to the left (4) until it clicks, making sure it is

locked firmly in place, to allow communication between the controller
and module.

7. Attach an end cap terminator (5) to the last module in the system by

using the tongue-and-groove slots as before.

8. Lock the end cap bus terminator (6).

Mount the Module

Minimum Spacing

Maintain spacing from enclosure walls, wireways, or adjacent equipment.
Allow 50 mm (2 in.) of space on all sides for adequate ventilation.

Space Requirements

ATTENTION

When attaching I/O modules, it is very important that
the bus connectors are securely locked together to be
sure of proper electrical connection.

IMPORTANT

A 1769-ECR or 1769-ECL right or left end cap must be used to
terminate the end of the bus.

ATTENTION

During panel or DIN rail mounting of all devices, be sure that all
debris (that is, metal chips or wire strands) is kept from falling
into the module. Debris that falls into the module could cause
damage when you cycle power.

Host Controller

Com

pact I/O

Com

pact I/O

Com

pact I/O

Com

pact I/O

Com

pact I/O

En

d Ca

p

Side

Side

Top

Bottom