Rockwell Automation 1769-BOOLEAN Compact I/O Module Reference Manual User Manual

Page 66

Advertising
background image

Publication 1769-RM016A-EN-P - July 2006

66 1769-BOOLEAN Module Specifications

Nominal Impedance

2.0 kohm @ 24V dc
2.3 kohm @ 30V dc

IEC Input Compatibility

Type 3

Input Point to Bus (CompactBus)
Isolation

Verified by one of the following dielectric tests: 1200V ac for 1
s or 1697V dc for 1 s
75V dc working voltage (IEC Class 2 reinforced insulation)

(1)

Sinking Input - Sink describes the current flow between the I/O module and the field device. Sinking I/O circuits are
driven by a current sourcing field device. Field devices connected to the positive side (+V) of the field supply are
sourcing field devices. Europe: DC sinking input and sourcing output module circuits are the commonly used options.

Attribute

Value

Advertising
This manual is related to the following products: