Input filtering – Rockwell Automation 1769-BOOLEAN Compact I/O Module Reference Manual User Manual

Page 47

Advertising
background image

Publication 1769-RM016A-EN-P - July 2006

Module Data, Status, and Configuration 47

The configuration file is typically modified using the programming software
configuration screen.

For information on how to configure the module using.

The configuration file can also be modified through the control program, if
supported by the controller.

Input Filtering

The 8 real inputs on the module are filtered using a common filter setting.
Word 0, bits 0

2 are used to select the input filtering level. A 3-bit pattern for

the filter time controls the filter setting for the input channels.

The default filter setting is 000 binary, selecting 8000

µs

.

IMPORTANT

Shaded bits must be set to 0. Default is all data file bits = 0.

Hardware and Software

See

MicroLogix 1500 and RSLogix 500 software

Appendix B

CompactLogix and RSLogix 5000 software

Appendix C

1769-ADN DeviceNet adapter and
RSNetWorx software

Appendix D

Word 0

Filter Time

Bit 2

Bit 1

Bit 0

0

0

0

8000 µs

0

0

1

0 µs

0

1

0

100 µs

0

1

1

200 µs

1

0

0

500 µs

1

0

1

1000 µs

1

1

0

2000 µs

1

1

1

4000 µs