Configure the module – Rockwell Automation 1769-BOOLEAN Compact I/O Module Reference Manual User Manual

Page 84

Advertising
background image

Publication 1769-RM016A-EN-P - July 2006

84 Configuration Using the RSLogix 5000 Generic Profile for CompactLogix Controllers

Tag addresses are automatically created for configured I/O modules. All local
I/O addresses are preceded by the word Local. These addresses have the
following format:

• Input Data: Local:s.I
• Output Data: Local:s.O
• Configuration Data: Local:s.C

where s is the slot number assigned the I/O modules in the Generic
Profiles.

To configure an I/O module, you must open up the configuration tag for that
module by clicking on the plus sign to the left of its configuration tag in the tag
database.

Configure the Module

Follow these instructions to configure the 1769-BOOLEAN module in slot 1.

1. Click on the plus sign left of Local:1.C.

Configuration data is entered under the Local:1.C.Data tag.

2. Click the plus sign to the left of Local:1.C.Data to reveal the 40 integer

data words where configuration data may be entered for the
1769-BOOLEAN module.

Refer to The 1769-BOOLEAN Module Configuration Data File on
page 46 for more information on configuration data word and bit
assignments.