Overview, Configuration method, Appendix d – Rockwell Automation 1769-BOOLEAN Compact I/O Module Reference Manual User Manual

Page 85: Overview configuration method, Appendix

Advertising
background image

85

Publication 1769-RM016A-EN-P - July 2006

Appendix

D

Configure Modules in a Remote DeviceNet
System with a 1769-ADN DeviceNet Adapter

Overview

In this example, the 1769-BOOLEAN module is in a remote DeviceNet
system controlled by a 1769-ADN DeviceNet adapter. RSNetWorx for
DeviceNet software, version 2.23 or later, is used to configure the network and
the I/O modules.

Configuration Method

The configuration method described here must be done prior to configuring
the DeviceNet adapter in the DeviceNet scanner’s scanlist. This applies if you
are configuring an I/O module offline, then downloading to the adapter, or if
you do the configuration online. After the adapter is placed in the scanner’s
scanlist, you can only configure or re-configure the I/O module using explicit
messages or by removing the adapter from the scanner’s scanlist, modifying
the configuration of the I/O module, and then adding the adapter back into
the scanner’s scanlist.

For additional information on configuring DeviceNet scanners and adapters,
the documentation for those products. The DeviceNet Adapter User Manual,
publication 1769-UM001, contains examples on modifying I/O module
configurations with explicit messages while the system is running.

Topic

Page

Configuration Method

85

Add the DeviceNet Adapter to the Scanlist

86

Configure the 1769-BOOLEAN Module Example

88

IMPORTANT

You must use a Series B 1769-ADN adapter with the
1769-BOOLEAN module.

TIP

After setting up each slot, be sure to choose Apply.

Advertising
This manual is related to the following products: