62 Module Diagnostics and Troubleshooting

Error Codes

Error codes can help troubleshoot your module.

1769-BOOLEAN Module Extended Error Codes

Error Type

Hex
Equivalent

(1)

Module
Error Code

Extended Error
Information
Code

Error Description

Binary

Binary

No Error

X000

000

0 0000 0000

No Error

General Common
Hardware Error

X200

001

0 0000 0000

General hardware error; no additional information

X201

001

0 0000 0001

Power-up reset state

Hardware Specific
Error

X300

001

0 1000 0000

General hardware error

X301

001

0 1000 0001

Microprocessor hardware error

X302

001

1 0000 0010

ASIC hardware error

Configuration
Error

X400

010

0 0000 0000

General configuration error; no additional
information

X401

010

0 0000 0001

Invalid output interrupt enable, OUT0

(3)

X402

010

0 0000 0010

Invalid output interrupt enable, OUT1

(3)

X403

010

0 0000 0011

Invalid output interrupt enable, OUT2

(3)

X404

010

0 0000 0100

Invalid output interrupt enable, OUT3

(3)

X405

010

0 0000 0101

Invalid Operand_A, OUT0

(4)

X406

010

0 0000 0110

Invalid Operand_A, OUT1

(4)

X407

010

0 0000 0111

Invalid Operand_A, OUT2

(4)

X408

010

0 0000 1000

Invalid Operand_A, OUT3

(4)