1769-boolean module input data file, 1769-boolean module output data file, Direct control of module outputs – Rockwell Automation 1769-BOOLEAN Compact I/O Module Reference Manual User Manual

Page 44

Advertising
background image

Publication 1769-RM016A-EN-P - July 2006

44 Module Data, Status, and Configuration

1769-BOOLEAN Module
Input Data File

The input data file lets you access module input read data for use in the control
program, via word or bit access. The data file structure is shown in the table
below. For each module, word 0, bits 0

7 in the input data file contain the

values of the real inputs. For each module, word 1, bits 0

3 in the input data

file contain the state of the module's output control circuits.

1769-BOOLEAN Module Input Data File

1769-BOOLEAN Module
Output Data File

The output data file lets you access module write data for use in the control
program, via word or bit access. The data file structure is shown in the table
below.

1769-BOOLEAN Output Data File

Direct Control of Module Outputs

The module's outputs can be directly determined by the control program
when the outputs are configured to have Boolean Control disabled.

Refer to Output Control (DB) on page 51, for information on configuring the
module's outputs for direct control mode.

When a module output has Boolean Control disabled, the directed state of that
output is controlled by the corresponding bit (OUT0 through OUT3) in the
output data file. Setting the bit (1) turns the output ON, clearing the bit (0)
turns the output OFF.

TIP

Shaded bits always must be set to 0.

WO

RD

Bit Position

15

14

13

12

1

10

9

8

7

6

5

4

3

2

1

0

0

IN7

IN6

IN5

IN4

IN3

IN2

IN1

IN0

1

03

02

01

00

TIP

Shaded bits must be set to 0.

Bit Position

15

14

13

12

1

10

9

8

7

6

5

4

3

2

1

0

WO

RD

0

OUT3 OUT2 OUT1 OUT0

1

V7

V6

V5

V4

V3

V2

V1

V0