10

Compact High-density Analog Voltage Input Module

Publication 1769-IN086A-EN-P - August 2008

Use the Dimensional Template

Locate holes every 17.5 mm (0.689 in.) to allow for a mix of single-wide and
one-and-a-half-wide modules (for example, the 1769-OA16 module).

Use Modules as a Template

This procedure lets you use the assembled modules as a template for drilling holes
in the panel. See

Use the Dimensional Template

if you have sophisticated panel

mounting equipment.

On a clean work surface, assemble no more than three modules.

Due to module-mounting hole tolerance, it is important to follow this procedure.

1. Using the assembled modules as a template, carefully mark the center of all

module-mounting holes on the panel.

2. Return the assembled modules to the clean work surface, including any

previously mounted modules.

3. Drill and tap the mounting holes for the recommended M4 or #8 screws.

4. Place the modules back on the panel, and check for proper hole alignment.

5. Attach the modules to the panel using the mounting screws.

6. Repeat steps 1…6 for any remaining modules.

TIP

If you are mounting more modules, mount only the last one of this
group and put the others aside. This reduces the remounting time
during drilling and tapping of the next group.

Spacing for single-wide modules 35 mm (1.378 in.)

Spacing for one-and-a-half wide modules 52.5 mm (2.067 in.)

Refer to host controller documentation for this dimension.

NOTE: Overall spacing
tolerance ±0.44 mm (0.016 in.)