Remove the finger-safe terminal block – Rockwell Automation 1769-IF16V Compact High Density Analog Voltage Input Module User Manual

Page 13

Advertising
background image

Compact High-density Analog Voltage Input Module 13

Publication 1769-IN086A-EN-P - August 2008

Wire Input Sensors/Transmitters

Label the Terminals

A removable, write-on label is provided with the module. Remove the label from
the door, mark the identification of each terminal with permanent ink, and slide the
label back into the door. Your markings (ID tag) will be visible when the module
door is closed.

Remove the Finger-safe Terminal Block

When wiring field devices to the module, it is not necessary to remove the terminal
block. If you remove the terminal block, use the write-on label on the side of the
terminal block to identify the module slot location and type.

To remove the terminal block, loosen the upper and lower retaining screws. The
terminal block will back away from the module as you remove the screws. When
replacing the terminal block, torque the retaining screws to 0.46 N

m (4.1 in

lbs).

+

IN1+

IN0+

IN3+

IN2+

IN5+

IN4+

IN7+

IN8+

IN6+

IN9+

IN11+

IN10+

IN12+

IN13+

IN15+

IN14+

Com

Com

+

+

-

Voltage
Transmitter

Sensor/
Transmitter
Power

(1)

Voltage Transmitter

Signal

Signal

Ground

1769-IF16V Terminal Block

(1) The sensor power supply must be rated Class 2.