System Wiring Guidelines

Consider the following when wiring your system:

•

All module commons (COM) are connected in the analog module.

•

The analog common (COM) is not connected to earth ground inside the
module.

•

Channels are not isolated from each other.

•

Use Belden 8761, or equivalent, shielded wire.

•

Under normal conditions, the drain wire and shield junction must be
connected to earth ground via a panel or DIN rail mounting screw at the
analog I/O module end. Keep the shield connection to ground as short as

possible.

(1)

•

To ensure optimum accuracy, limit overall cable impedance by keeping your
cable as short as possible. Locate the I/O system as close to your sensors or

actuators as your application will permit.

(2)

•

If multiple power supplies are used with analog inputs, the power supply
commons must be connected.

•

The 1769-IF16V module does not provide loop power for analog inputs. Use
a Class 2-rated power supply that matches the input transmitter
specifications.

•

Voltages on the IN+ terminals of the 1769-IF16V module must be within
±10V DC of analog common.

(1) In environments where high-frequency noise may be present, it may be necessary to directly ground cable shields to earth

at the module end and via a 0.1 µF capacitor at the sensor end.

(2) Cable length over 50 m (164 ft) may impact accuracy. For details, refer to the Compact High-Density Analog Input Modules

User Manual, publication

1769-UM018.

ATTENTION

Be careful when stripping wires. Wire fragments that fall into a
module could cause damage at power up. Once wiring is complete,
ensure the module is free of all metal fragments.