Configure the 1769-if16v module, Output data file – Rockwell Automation 1769-IF16V Compact High Density Analog Voltage Input Module User Manual
Page 15

Compact High-density Analog Voltage Input Module 15
Publication 1769-IN086A-EN-P - August 2008
Configure the 1769-IF16V Module
Use the following I/O memory mapping tables to configure the 1769-IF16V
module.
Output Data File
For each module, slot x, words 0 and 1 in the output data file contain the cancel
latched channel alarm control bits.
The bits are defined as follows:
•
CLH
x = Cancel High Process Alarm Latch for Input x: Allows each input
high-process-alarm latch to be individually cancelled. Cancel = 1.
•
CLL
x = Cancel Low Process Alarm Latch for Input x: Allows each input
low-process-alarm latch to be individually cancelled. Cancel = 1.
Word/
Bit
15
14
13
12
11
10
09
08
07
06
05
04
03
02 01 00
Word 0 CL
L7
CL
H7
CL
L6
CL
H6
CL
L5
CL
H5
CL
L4
CL
H4
CL
L3
CL
H3
CL
L2
CL
H2
CL
L1
CL
H1
CL
L0
CL
H0
Word 1 CL
L15
CL
H15
CL
L14
CL
H14
CL
L13
CL
H13
CL
L12
CL
H12
CL
L11
CL
H11
CL
L10
CL
H10
CL
L9
CL
H9
CL
L8
CL
H8