Configuration data file – Rockwell Automation 1769-IF16V Compact High Density Analog Voltage Input Module User Manual

Page 17

Advertising
background image

Compact High-density Analog Voltage Input Module 17

Publication 1769-IN086A-EN-P - August 2008

The bits are defined as follows:

SGN = Sign bit in 2’s complement format.

Nu = Not Used. Bit set to 0.

S

x = General Status bit for input channels 0…15.

O

x = Over range flag bits for input channels 0…15.

U

x = Under range flag bits for input channels 0…15.

H

x = High Alarm flag bits for input channels 0…15.

L

x = Low Alarm flag bits for input channels 0…15.

Configuration Data File

The manipulation of bits from this file is normally done with programming software
(for example, RSLogix 5000, RSLogix 500, or RSNetWorx for DeviceNet software)
during initial configuration of the system. In that case, graphical screens provided
by the programming software simplify configuration.

Some systems, like the 1769-ADN DeviceNet adapter system, also allow the bits to
be altered as part of the control program using communication rungs. In that case,
it is necessary to understand the bit arrangement.

Configuration Data Array

Word/Bit 15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Word 0

0

Real Time Sample Value

Word 1

ETS

Reserved

Word 2

EC

Reserved

EA

AL

EI

(1)

Reserved

Input Filter Sel Ch0

Word 3

Reserved

Input Data
Format Ch0

Reserved

Input Type/Range
Select Ch0

Word 4

SGN Process Alarm High Data Value Channel 0

Word 5

SGN Process Alarm Low Data Value Channel 0

Word 6

SGN Alarm Dead Band Value Channel 0

Word 7

Reserved

Word 8

EC

Reserved

EA

AL

EI

(1)

Reserved

Input Filter Sel Ch1

Word 9

Reserved

Input Data
Format Ch1

Reserved

Input Type/Range
Select Ch1

Word 10 SGN Process Alarm High Data Value Channel 1

Word 11 SGN Process Alarm Low Data Value Channel 1

Word 12 SGN Alarm Dead Band Value Channel 1

Word 13 Reserved

Advertising