Rockwell Automation 1756-CN2RXT ControlLogix-XT ControlNet Interface Module, Series B Installation Instructions User Manual
Page 25

ControlLogix-XT ControlNet Interface Module 25
Publication
1756-IN634A-EN-P - April 2009
Flashing
red
Image
update
Needed
Boot image running.
Main firmware image needs
to be updated.
Update the module’s firmware
by using the ControlFlash
utility.
DUPLICATE
NODE
DETECTED
The module’s network address
is the same as another
module’s on the link.
1. Remove power from the
chassis.
2. Remove the module from
the chassis.
3. Set the switches to their
final value. See
4. Replace the module in the
chassis.
5. Apply power to the chassis.
Flash in
progress
Flash update is in progress.
No action is required.
If communication to the
module is lost during a Flash
Update, this message will
continue to be displayed even
though the module will not be
able to finish the update.
You must remove power from
the module to recover, and
then flash again.
TEST
Module is executing a
power-up test.
No action is required.
If the display persists for more
than 45 seconds, replace the
module because it has failed.
OK
Indicator
Display
Cause
Recommended Action