ControlLogix-XT ControlNet Interface Module 25

Publication

1756-IN634A-EN-P - April 2009

Flashing
red

Image
update
Needed

Boot image running.

Main firmware image needs
to be updated.

Update the module’s firmware
by using the ControlFlash
utility.

DUPLICATE
NODE
DETECTED

The module’s network address
is the same as another
module’s on the link.

1. Remove power from the

chassis.

2. Remove the module from

the chassis.

3. Set the switches to their

final value. See

page 11

.

4. Replace the module in the

chassis.

5. Apply power to the chassis.

Flash in
progress

Flash update is in progress.

No action is required.

If communication to the
module is lost during a Flash
Update, this message will
continue to be displayed even
though the module will not be
able to finish the update.

You must remove power from
the module to recover, and
then flash again.

TEST

Module is executing a
power-up test.

No action is required.

If the display persists for more
than 45 seconds, replace the
module because it has failed.

OK
Indicator

Display

Cause

Recommended Action