Environmental specifications - 1756-cn2rxt – Rockwell Automation 1756-CN2RXT ControlLogix-XT ControlNet Interface Module, Series B Installation Instructions User Manual

Page 32

Advertising
background image

32 ControlLogix-XT ControlNet Interface Module

Publication

1756-IN634A-EN-P - April 2009

Environmental Specifications - 1756-CN2RXT

Attribute

Value

Temperature, Operating

IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal
Shock)

-25…70 °C (-13…158 °F)

Temperature, Nonoperating

IEC 60068-2-1 (Test Ab, Unpackaged

Nonoperating Cold),

IEC 60068-2-2 (Test Bb, Unpackaged

Nonoperating Dry Heat),

IEC 60068-2-14 (Test Na, Unpackaged

Nonoperating Thermal Shock)

-40…85 °C (-40…185 °F)

Relative Humidity

IEC 60068-2-30 (Test Db, Unpackaged Damp
Heat)

5…95% noncondensing

Vibration

IEC 60068-2-6 (Test Fc, Operating)

2 g @ 10…500 Hz

Operating Shock

IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, Non-operating

IEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g

Emissions

CISPR 11

Group 1, Class A

ESD Immunity

IEC 61000-4-2

6 kV contact discharges

8 kV air discharges