ControlLogix-XT ControlNet Interface Module 27

Publication

1756-IN634A-EN-P - April 2009

Solid or
flashing
green

CPU=XX%

This message is the CPU
utilization rate where XX is
the amount of CPU used,
ranging from 0...99%. This
message occurs only if the
CPU utilization exceeds 80%.

No action is required.

OK

Module is operating normally.

No action is required.

Flashing
green

OK

This is normal operation.

No connections to or through
the module exist. No action is
required.

Invalid
Network
Configuration

ControlNet configuration error. Recheck configuration.

Verify that the module’s
network address is less than or
equal to the maximum
unscheduled network address
(UMAX).

NET

ERR

A network cabling error exists,
or there are no other active
nodes on the network.

Recheck your network cabling
and make sure another node
on the network is active
(online).

Rev XX.XX

When you start the module,
its major and minor revisions
are disclosed, causing this
message to briefly appear.

The display shows these
revisions where the major
revision appears to the left of
the decimal point, and the
minor revision to the right.

No action is required.

OK
Indicator

Display

Cause

Recommended Action