Rockwell Automation 1756-CN2RXT ControlLogix-XT ControlNet Interface Module, Series B Installation Instructions User Manual

Page 9

Advertising
background image

ControlLogix-XT ControlNet Interface Module 9

Publication

1756-IN634A-EN-P - April 2009

Using the 1756-CN2RXT for Standalone or Redundant Control

You can use the 1756-CN2RXT modules either in standalone or
redundant configurations.

A standalone configuration uses:

• one control chassis that contains the 1756-CN2RXT and the

1756-L63XT controller.

• one or both channels of the 1756-CN2RXT module connected

to the ControlNet network.

A redundant configuration uses:

• two controller chassis called the redundant chassis pair. Each

chassis of the pair must contain at least these modules:

– 1756-L63XT controller.

– 1756-CN2RXT ControlNet module.

– 1756-RMXT redundancy module.

• one or both channels of the 1756-CN2RXT module connected

to the ControlNet network.

For more information about redundancy control, refer to the
ControlLogix Redundancy System User Manual, publication

1756-UM523

.

IMPORTANT

If you are using the 1756-CN2RXT in a redundant system, these hardware
considerations must be made:

•

Each redundant chassis of the pair must be configured with identical
modules placed in identical slots. These module pairings between the
two chassis are called partners.

•

All partner modules in redundant chassis pairs must be at the same
firmware revision.

•

For ControlNet module partners, the ControlNet network address must
be the same for each module of the pair.

•

These modules cannot be used in redundant chassis pairs that contain
1756-CN2RXT modules:

– 1756-DHRIOXT or 1756-DHRIO

– 1756-SRM