28 ControlLogix-XT ControlNet Interface Module

Publication

1756-IN634A-EN-P - April 2009

Any

Keeper:
Unconfigured

The network configuration
data maintained in flash
memory by the keeper object
has been erased or corrupted.

Perform any of these steps:

·

Use RSNetWorx software to
download or update the
keeper object in the module.

·

See Reset the Module to
the Original Factory
Settings, on

page 12

.

Keeper:
Unconfigured
(data format
changed)

The network configuration
data maintained in flash
memory by the keeper object
is in a format incompatible
with the current revision of
firmware.

Perform any of these steps:

·

Use RSNetWorx software to
download or update the
keeper object in the module.

·

See Reset the Module to
the Original Factory
Settings, on

page 12

.

Keeper:
Unconfigured
(slot
changed)

After the keeper object’s
network-configuration data
was downloaded, the module
was moved to a different spot
in the chassis.

Perform any of these steps:

·

Return the module to the
proper slot.

·

Use RSNetWorx software to
download or update the
keeper object in the module.

·

See Reset the Module to
the Original Factory
Settings, on

page 12

.

Keeper:
Unconfigured
(net address
changed)

The network address switches
on the module have been
changed since the keeper
object’s network-configuration
data was downloaded.

Perform any of these steps:

·

Return the network address
switches to their original
setting.

·

Use RSNetWorx software to
download or update the
keeper object in the module.

·

See Reset the Module to
the Original Factory
Settings, on

page 12

.

OK
Indicator

Display

Cause

Recommended Action