ControlLogix-XT ControlNet Interface Module 33
Publication
1756-IN634A-EN-P - April 2009
Radiated RF Immunity
IEC 61000-4-3
•
10V/m with 1 kHz sine-wave 80%
AM from 80…2000 MHz
•
10V/m with 200 Hz 50% Pulse
100% AM at 900 MHz
•
10V/m with 200 Hz 50% Pulse
100% AM at 1890 MHz
•
3V/m with 1 kHz sine-wave 80%
AM from 2000…2700 MHz
EFT/B Immunity
IEC 61000-4-4
±2 kV at 5 kHz on ControlNet ports
Surge Transient Immunity
IEC 61000-4-5
±1 kV line-earth(CM) on
communications ports
Conducted RF Immunity
IEC 61000-4-6
10V rms with 1 kHz sine-wave 80%
AM from 150 kHz…80 MHz