Restore the Factory Default Settings

The out-of-box reset will clear the scanlist (including ADR configuration
recovery files) and return all software setting attributes to their default values.
Follow this procedure to restore the factory default communication rate and
node address.

1. Set the switches to 888.

2. Restore power to the module.

When the out-of-box reset is complete, the alphanumeric display
repeatedly scrolls the message Reset Complete - Change Switch
Settings. During this time, the module does not respond to
communication from any port (including the backplane, DeviceNet
connector, or USB port).

3. After the module resets, perform the following steps.

a. Set the switches to the desired position.
b. Restore power to the module.

IMPORTANT

Do not use the 888 switch setting during normal module operation.