The status structure consists of these data elements.
Status Structure
Element
Description
Data
Type
DINTS
ScanCounter
Counter incremented each I/O scan
32-bit
10
DeviceFailureRegister
Device failed bit table; 1 = failed
64-bit
AutoverifyFailureRegister
Device I/O size does not match
scanner’s internal table;
1 = mismatch
64-bit
DeviceIdleRegister
Device is idle bit table; 1 = idle
64-bit
ActiveNodeRegister
Node online bit table; 1 = online
64-bit
StatusDisplay
ASCII representation of scanner
module alphanumeric display
4-byte
ScannerDeviceStatus
Scanner device status:
4-byte
binary
11
ScannerAddress
DeviceNet address of1756- DNB
scanner module
8-bit
binary
ScannerStatus
Status of 1756-DNB scanner module
8-bit
binary
ScrollingDeviceAddress
Scrolls through DeviceNet nodes
once per s by address and status
(0 = no faults).
8-bit
binary
ScrollingDeviceStatus
8-bit
binary
ReservedArray
Future expansion (20 bytes)
20 x
8-bit
16
DeviceStatus
DeviceNet node status array,
byte per device
64 x
8-bit
24/32