Specifications – Rockwell Automation 1756-DNB ControlLogix DeviceNet Scanner Module Installation Instructions User Manual
Page 43

ControlLogix DeviceNet Scanner Module 43
Publication
1756-IN566D-EN-P - June 2008
Specifications
ControlLogix DeviceNet Scanner Module, Cat. No. 1756-DNB
Attribute
Value
Module location
Any slot in the ControlLogix chassis
DeviceNet communication
rate, max
125 Kbps - 500 m (1640 ft.) max
250 Kbps - 250 m (820 ft.) max
500 Kbps - 100 m (328 ft.) max
Backplane current (mA) at
5.1V DC
850 mA
Backplane current (mA) at
24V DC
3 mA
DeviceNet current (mA),
max
11…25V DC (60 mA max)
Isolation voltage,
continuous
30V (continuous), Basic Insulation Type
No isolation between USB and system
Tested at 500V AC for 60 s, DeviceNet to system
Enclosure type rating
None (open-style)
Conductors
Wire size
Category
Refer to the DeviceNet Media Design and Planning Guide,
publication
, for information specific to your
DeviceNet network.
(1)
North American temp code
T4A
IEC temp code
T4
Power dissipation, max
5.8 W
Thermal dissipation, max
19.8 BTU/hr
Recommended USB cable
for USB port
Samtec cable, PN RSP-119350