ControlLogix DeviceNet Scanner Module 37

Publication

1756-IN566D-EN-P - June 2008

Indicator

State

Description

Module/

Network
(MOD/NET)

Flashing

red

(1)

Minor fault and/or connection time-out - recoverable fault
and/or one or more I/O connections are in the timed-out state.

Red

Critical fault or critical link failure - device has an
unrecoverable fault and may need to be replaced.

Failed communication device. The device has detected an
error (duplicate MAC ID or bus-off) that has rendered it
incapable of communicating on the network.

I/O

Off

Scanner is not online. Check network power.

Green

Scanner is in RUN mode, outputs are under control, and inputs
are being consumed.

Flashing

green

(1)

(1)

The flash rate of the status indicator is approximately 1 flash per second. The status indicator should
be on for approximately 0.5 seconds and off for approximately 0.5 seconds.

Scanner is in IDLE mode, outputs are not under control, and
inputs are being consumed.

OK

Off

No power applied to device. Apply chassis power. Verify
module is completely inserted into chassis and backplane.

Green

Device is operating normally. The 1756-DNB scanner module
has at least one connection to it from a controller.

Flashing

green

(2)

(2)

The flash rate of the status indicator is approximately 1 flash per second. The status indicator should
be on for approximately 0.5 seconds and off for approximately 0.5 seconds.

The device is operating correctly; however, no controller is
controlling it. Verify that the 1756-DNB scanner module is
properly configured in the controller’s I/O configuration.

Red

Device has an unrecoverable fault; repair or replace it, or

Device is in self test during power-up.