28 ControlLogix DeviceNet Scanner Module

Publication

1756-IN566D-EN-P - June 2008

Alphanumeric Status Messages

The following table summarizes the status messages.
Alphanumeric Status Message

Status Message

Description

Run

The 1756-DNB scanner module is in Run mode.

Idle

The 1756-DNB scanner module is in Idle mode.

Auto

AutoScan is enabled and the 1756-DNB scanner module is in Idle
mode.

Flash In Progress

ControlFlash is transferring a flash image to the 1756-DNB scanner
module.

Duplicate Node
Failure

The node address of the 1756-DNB scanner module is already in
use by another device on the DeviceNet network.

Bus Off Detected

The 1756-DNB scanner module has detected errors on the
DeviceNet network and has been taken offline.

No Network Power

No DeviceNet network power is being supplied to the 1756-DNB
scanner module.

NoRX

- The 1756-DNB scanner module does not contact a scanlist.

- The 1756-DNB scanner module has not received communication
from any other device.

NoTX

The 1756-DNB module failed to transmit a message.

Reset Complete -
Change Switch
Settings

Factory default settings for the 1756-DNB module have been
restored. Set the data rate and node address rotary switches to the
desired position and restore power to the module.