Rockwell Automation 1756-DNB ControlLogix DeviceNet Scanner Module Installation Instructions User Manual

Page 30

Advertising
background image

30 ControlLogix DeviceNet Scanner Module

Publication

1756-IN566D-EN-P - June 2008

74

Scanner detected data overrun on
DeviceNet communication port.

• Modify your configuration and check

for invalid data.

• Check network communication

traffic.

75

Either or both of the following:

• The device does not have a

scan list.

• The device has not received

communication from any other
device.

Verify that the device has a:

• configured scan list.

• properly-wired connection to the

network.

76

No direct network traffic for
scanner. The scanner hears other
network communication but does
not hear any directed to it.

None.

77

During initialization, the data size
expected by the device does not
match the scan list entry.

Use RSNetWorx for DeviceNet software
to check the slave device and the scan list
for the correct input and output sizes for
the slave device.

DeviceNet Status Codes

Status
Code

Description of Status

Recommended Action

Advertising