Rockwell Automation 1756-DNB ControlLogix DeviceNet Scanner Module Installation Instructions User Manual

Page 29

Advertising
background image

ControlLogix DeviceNet Scanner Module 29

Publication

1756-IN566D-EN-P - June 2008

DeviceNet Status Codes

The following table summarizes the codes.

DeviceNet Status Codes

Status
Code

Description of Status

Recommended Action

0..63

Scanner’s DeviceNet node address.

None.

65

The AutoScan option is on and the
device is in Idle mode.

None.

67

Scanner is secondary scanner.

None.

68

Primary scanner has detected no
secondary scanner.

Configure another scanner to be the
secondary scanner.

69

Primary and secondary
configurations are mismatched.

Check configuration of the secondary
scanner.

70

The address of the device is already
in use by another device on the
network. The scanner failed the
duplicate node address check.

Change the address of the device to an
unused address.

71

Invalid data in scan list.

Use RSNetWorx for DeviceNet software
to reconfigure the scan list.

72

Slave device stopped
communicating. If the slave device
does not recover communication
during next scan, status code
changes to 78.

Verify slave device’s:

• power.
• communication connections.

If slave device is polled, verify that
interscan delay time is adequate for the
device to return data.

73

Slave device’s identity information
does not match electronic key in
scanner.

• Make sure that the correct device is

connected at this address.

• Make sure that the device matches

the specified electronic key (vendor,
product code, and product type).

Advertising