Rockwell Automation 1756-DNB ControlLogix DeviceNet Scanner Module Installation Instructions User Manual

Page 32

Advertising
background image

32 ControlLogix DeviceNet Scanner Module

Publication

1756-IN566D-EN-P - June 2008

82

Error detected in sequence of
fragmented I/O messages from
device.

Use RSNetWorx for DeviceNet software
to:

• check scan list of the device to make

sure that its input and output data
sizes are correct.

• check the configuration of the device.

83

Device returns error responses
when the scanner attempts to
communicate with it.

• Use RSNetWorx for DeviceNet

software to:

check the accuracy of the scan

list.

check the configuration of the

device. The device may be in
another scanner’s scan list.

• Use the slave device’s documentation

to verify that the device supports the
message type used by the scanner.

If the device’s message type does

not match the scanner’s, then use
RSNetWorx for DeviceNet
software to access the scanner’s
scanlist and change the scanner’s
message type to one that is
compatible with the slave device.

• Cycle power to the device.

84

Scanner is initializing the DeviceNet
network.

None. This code clears itself once the
scanner attempts to initialize all the
devices on the network.

DeviceNet Status Codes

Status
Code

Description of Status

Recommended Action