Wiring your input module – Rockwell Automation 1771-IFE , D17716.5.90 USER MNL. ANALOG INPUT Module User Manual

Page 15

Advertising
background image

Installing the Input Module

Chapter 2

2-3

Figure 2.1

Keying Positions

2
4
6
8
1 0
1 2
1 4
1 6
1 8
2 0
2 2
2 4
2 6
2 8
3 0
3 2
3 4
3 6

Keying

Bands

1771ĆIFE

12676

Connect your I/O devices to the cat. no. 1771-WG wiring arm shipped
with the module. Attach the wiring arm to the pivot bar at the bottom of
the I/O chassis. It pivots upward and connects with the module so you can
install or remove the module without disconnecting the wires.

Input connections for the 1771-IFE with single-ended inputs are shown in
Figure 2.2 and Figure 2.3. Input connections for the 1771-IFE with
differential inputs are shown in Figure 2.4 and Figure 2.5.

Recommended maximum cable length for voltage-mode input devices is
50 feet. This recommendation is based on considerations of signal
degradation and electrical noise immunity in typical industrial
environments. Cable length for current-mode input devices need not be as
restrictive because analog signals from these devices are less sensitive to
electrical noise interference.

The 1771-IFE module is shipped from the factory set for a 1 to 5V DC
voltage input.
Refer to “Changing Your Module’s Configuration”on page
2-9 for other combinations of current and voltage inputs.

Wiring Your Input Module